Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 191
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
191
Communication
Chapter 9
For an explicit message using a DeviceNet or ControlNet network, only the
communication path changes, as shown below.
Path
This field specifies the communication path from the controller to the power
monitor. Set-up the path as <Backplane (always 1), Slot of Communication
Module, Port (2 for Ethernet and DeviceNet networks), power monitor IP
Address or DeviceNet address>.
Communication Method
For PLC-5 and SLC Typed Reads, this always defaults to CIP.
RSLogix 5000 Software – PLC-5 or SLC Typed Write Message Setup
A write message is very similar to the PLC-5 and SLC Type read message
described above. The changes are in the Configuration tab, as follows.
Message Type
These are the choices:
PLC-5 Typed Write
SLC Typed Write
Source Element
This field specifies the controller tag in which to store the data to write to the
power monitor.