Logged parameters – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 142

Advertising
background image

142

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Chapter 6

Logging

Logged Parameters

The event log operates in a circular, or FIFO fashion. When accessed as a file, the
first record is a header containing the tag names. Each subsequent record is a
structure of REAL elements containing the following parameters.

Tag Name

Description

Record_Identifier

Used to verify record sequence when returning multiple records

Event_Type

Power quality event type, see Power Quality Event Code table.

Sub_Event_Code

Indicate the sub event of the event type. For example, a sag event can happen in V1, V2 or V3. See Power Quality Event Code table.

Local_Timestamp_Year

Year of the local time when the record was recorded

Local_Timestamp_Mth_Day

Month and Day of the local time when the record was recorded

Local_Timestamp_Hr_Min

Hour and Minute of the local time when the record was recorded

Local_Timestamp_Sec_mS

Second and Millisecond of the local time when the record was recorded.

Local_Timestamp_uS

Microsecond when the record was recorded

UTC_Timestamp_Year

Year of the UTC when the record was recorded

UTC_Timestamp_Mth_Day

Month and Day of the UTC when the record was recorded

UTC_Timestamp_Hr_Min

Hour and Minute of the UTC when the record was recorded.

UTC_Timestamp_Sec_mS

Second and Millisecond of UTC when the record was recorded.

UTC_Timestamp_uS

Microsecond of UTC when the record was recorded.

Association_Timestamp_Year

Year of the timestamp associated with waveform file if the event can trigger a waveform capture

Association_Timestamp_Mth_Day

Month and Day of the timestamp associated with waveform file if the event can trigger a waveform capture

Association_Timestamp_Hr_Min

Hour and Minute of the timestamp associated with waveform file if the event can trigger a waveform capture

Association_Timestamp_Sec_mS

Second and Millisecond of the timestamp associated with waveform file if the event can trigger a waveform capture

Association_Timestamp_uS

Microsecond of the timestamp associated with waveform file

Event_Duration_mS

Event duration in milliseconds for a sag or swell event, Event duration in cycles for WSB events

Min_or_Max_Volts

Minimum value of a sag or maximum value of a swell

Trip_Point

The trip point that triggered the event

WSB Originator

ID of the unit that originated the WSB message; the 3 least significant bytes of its MAC ID