Command, Wiring diagnostic results – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 55

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

55

Metering

Chapter 4

Command

Command Word 2

Set this command word value to 11 (decimal) or make selection in web page to
initiate wiring diagnostics.

Wiring Diagnostic Results

The PowerMonitor 5000 unit returns the following wiring diagnostic results for
all three power factor ranges. Results are available for about 5 minutes after the
command is received.

Command_Status

These are the values:

0 = Command Active
1 = Input Level Low
2 = Disabled
3 = Waiting Command

RangeN_Voltage_Input_Missing
RangeN_Current_Input_Missing

These are the values for these parameters:

-1 = Test not run
0 = Test passed
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing

Range1_L97_C89_Status
Range2_L85_C98_Status
Range3_L52_L95_Status

0 = pass
1 = fail

Advertising