Loggingresults.alarm_log – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 341

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

341

PowerMonitor 5000 Unit Data Tables

Appendix A

LoggingResults.Alarm_Log

Table 153 - Table Properties

CIP Instance Number

856

PCCC File Number

N65

No. of Elements

7

Length in Words

7

Data Type

Int16

Data Access

Read Only

Table 154 - LoggingResults.Alarm_Log Data Table

Element
Number

Type

Tag Name

Description

Unit

Range

0

Int16

Alarm_Record_Identifier

Used to verify record sequence when returning multiple records.

1…100

1

Int16

Alarm_Timestamp_Year

The year when the record was recorded.

YYYY

2010…2100

2

Int16

Alarm_Timestamp_Mth_Day

The month and day when the record was recorded.

MMDD

11…1231

3

Int16

Alarm_Timestamp_Hr_Min

The hour and minute when the record was recorded.

HHMM

0…2359

4

Int16

Alarm_Timestamp_Sec_ms

The seconds and milliseconds when the record was recorded.

SSms

0…59,999

5

Int16

Alarm Type

Indicates the type of event that has occurred.

0…512

6

Int16

Alarm Code

Indicates information about the alarm.

0…4096

Advertising