Loggingresults.setpoint_log – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 343

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

343

PowerMonitor 5000 Unit Data Tables

Appendix A

LoggingResults.Setpoint_Log

Table 157 - Table Properties

CIP Instance Number

858

PCCC File Number

F67

No. of Elements

18

Length in Words

36

Data Type

Real

Data Access

Read Only

Table 158 - LoggingResults.Setpoint_Log Data Table

Element
Number

Type

Tag Name

Description

Unit

Range

0

Real

Setpoint_Record_Identifier

Used to verify record sequence when returning multiple records.

1…100

1

Real

Setpoint_Timestamp_Year

The year when the record was recorded.

YYYY

2010…2100

2

Real

Setpoint_Timestamp_Mth_Day

The month and day when the record was recorded.

MMDD

11…1231

3

Real

Setpoint_Timestamp_Hr_Min

The hour and minute when the record was recorded.

HHMM

0…2359

4

Real

Setpoint_Timestamp_Sec_ms

The seconds and milliseconds when the record was recorded.

SSms

0…59,999

5

Real

Setpoint_Number

Setpoint number of record.

0…20

6

Real

Setpoint_Status

Setpoint is active (1) or not active (0).

0…1

7

Real

Input_Parameter

Input test parameter of setpoint.

0…105

8

Real

Test_Condition

Test Condition.

0…3

9

Real

Evaluation_Type

Evaluation type for setpoint.

1…3

10

Real

Threshold_Setting

The threshold setting magnitude or percent.

0.000…
10,000,000

11

Real

Hysteresis_Setting

Magnitude or percent

0.000…
10,000,000

12

Real

Assert_Delay

Time delay before actuation.

seconds

0.000…3600

13

Real

Deassert_Delay

Time delay before deassert.

seconds

0.000…3600

14

Real

Output_Source

Output flag or bit.

0…40

15

Real

Output_Action

Configured action when actuated.

0…TBD

16

Real

Accumulated_Time

Total accumulation in seconds.

seconds

0.000…
10,000,000

17

Real

Number_Of_Transitions

Number of transitions from off to on.

0…10,000,000

Advertising