Setup, Optional controlnet communication – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 183

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

183

Communication

Chapter 9

Setup

Setup parameters for the optional DeviceNet port are found in the

Configuration.OptionalComm.DNT

table.

Mac ID

Selects the DeviceNet node address. The range is 0…63 (default).

Communication Rate

Selects the DeviceNet network communication (data) rate, and must be selected
to match the remaining devices on the network. The selections are the following:

0 = 125 Kbps

1 = 250 Kbps

2 = 500 Kbps

3 = Autobaud

Optional ControlNet
Communication

PowerMonitor 5000 units can be optionally equipped with a ControlNet
communication port. A ControlNet communication port can be factory
installed or field installed by you. The ControlNet network is an open-standard,
multi-vendor, industrial device data network that supports scheduled, I/O
communication as well as unscheduled messaging. The ControlNet port and the
native Ethernet port can be used simultaneously.

Setup

The

Configuration.OptionalComm.CNT

table contains the Address tag, the

only setup parameter. Valid ControlNet addresses range from 1…99. The default
value is 255.