Setpoint logic gates (m6 model), Equal to – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 160

Advertising
background image

160

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Chapter 7

Logic Functions

Equal To

An Equal To test condition arms the setpoint for activation when the monitored
value exactly equals the threshold, and dis-arms the setpoint when the value no
longer equals the threshold. Hysteresis is ignored in the Equal To test condition.

Figure 25

illustrates this. In

Figure 25

e, the setpoint is armed at point A, dis-

armed at point B, and armed at point C. Point d also arms the setpoint but the
value changes at point e before the assert delay time passes.

Figure 25 - Equal To Test Condition

Setpoint Logic Gates (M6 model)

Up to 10 logic gates can be used to logically combine setpoints to enable output
actions. Each logic gate can have up to four inputs. Select among AND, NAND,
OR, NOR, XOR or XNOR logic. XOR and XNOR use inputs 1 and 2.

In

Figure 26

, Setpoint Output 1 activates when Setpoint 1 asserts. Setpoint

Output 2 activates when both Setpoint 1 and Setpoint 2 assert.

Figure 26 - Setpoint Example

Assert

Delay

Deassert

Delay

Output

Threshold

A

B

C

d

e

Assert

Delay

Setpoint 1

·

Parameter Selection 1

·

Reference Value 1

·

Test Condition 1

·

Evaluation Type 1

·

Threshold 1

·

Hysteresis 1

·

Assert Delay Seconds 1

·

Deassert Delay Seconds 1

Setpoint 2

·

Parameter Selection 2

·

Reference Value 2

·

Test Condition 2

·

Evaluation Type 2

·

Threshold 2

·

Hysteresis 2

·

Assert Delay Seconds 2

·

Deassert Delay Seconds 2

Logic Gate 1

·

Logic Level 1 Gate 1
Function: AND

·

L 1 _ G1 Input

1 : Setpoint

1

·

L 1 _ G1 Input

2 : Setpoint

2

·

L 1 _ G1 Input

3 : Disabled

·

L 1 _ G1 Input

4 : Disabled

Setpoint Output 1

Setpoint Output 1 Input Source : Setpoint 1

Setpoint Output 1 Action

Setpoint Output 2

Setpoint Output 2 Input Source : Logic Gate

1

Setpoint Output 2 Action

Advertising