Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

11

Int16

L1_G3 Input 1

Selects the first input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3

20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.

0

-20…20

12

Int16

L1_G3 Input 2

Selects the second input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3

20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.

0

-20…20

13

Int16

L1_G3 Input 3

Selects the third input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3

20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.

0

-20…20

14

Int16

L1_G3 Input 4

Selects the fourth input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3

20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.

0

-20…20

15

Int16

Logic Level 1
Gate 4 Function

Selects the logic type
0 = disabled,
1 = AND
2 = NAND
3 = OR
4 = NOR
5 = XOR
6 = XNOR
IMPORTANT: XOR and XNOR use Inputs 1 and 2 only.

0

0…6

16

Int16

L1_G4 Input 1

Selects the first input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3

20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.

0

-20…20

Table 70 - Configuration.Setpoint_Logic Data Table

Element
Number

Type

Tag Name

Description

Default

Range