PowerMonitor 5000 Unit Data Tables

Appendix A

72

2

INT

ForcedDemandSyncDelay

When the power monitor is configured for external demand control
the unit delays for xxx seconds after the expected control pulse has
not been received. The demand period starts over and a record is
recorded in the status log
0 = Wait forever
1…900 = Wait this many seconds before starting a new demand
period.
IMPORTANT: This setting becomes active when an external input is
used to end the demand period.

Demand
Broadcast
Mode

0…900

2

INT

Pad16

For alignment purpose

76

1

SINT

DemandBroadcastMode

Demand Ethernet broadcast selection.
0 = Slave
1 = Master
IMPORTANT: There can be only one master per demand network.

Demand
Broadcast
Mode

0…1

1

SINT

Pad17

For alignment purpose

78

2

INT

DemandBroadcastPort

The common port for demand broadcast messages.

Demand
Broadcast Port

300…400

80

1

SINT

KYZOutputMode

The parameter selected pulses the KYZ output at a rate that equals the
parameter value divided by KYZ scale.
0 = Setpoint Control
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah

KYZ Output
Parameter

0…6

1

SINT

Pad18

For alignment purpose

2

INT

Pad19

For alignment purpose

84

4

DINT

KYZPulseScale

The KYZ output parameter divided by the scale is the output pulse
rate. Example: Wh is selected for the parameter and 1,000 is the
scale value. The output is pulsed every kWh.

KYZ Output
Scale

1…100,000

88

2

INT

KYZPulseDuration

Set as 50…1000 to indicate the duration of the pulse in milliseconds,
or set to 0 for KYZ-style transition output. (Toggle)
IMPORTANT: The value for delay is rounded off to the nearest 10 ms
internally during this function.

KYZ Output
Duration

0 or 50…1000

2

INT

Pad20

For alignment purpose

92

1

SINT

R1OutputMode

The parameter selected will pulse the relay 1 output at a rate that
equals the parameter value divided by relay 1 scale.
0 = Setpoint Control
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah

Relay 1 Output
Parameter

0…6

1

SINT

Pad21

For alignment purpose

2

INT

Pad22

For alignment purpose

96

4

DINT

R1PulseScale

The relay 1 output parameter divided by the relay 1 scale is the output
pulse rate. Example: Wh is selected for the parameter and 1,000 is the
scale value. The output is pulsed every kWh.

Relay 1 Output
Scale

1…100,000

Table 44 - Configuration.Instance Data Table

Start
Byte

Size Type

Tag

Name

Description

Units

Range