284
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A
PowerMonitor 5000 Unit Data Tables
Configuration.OptionalComm.DNT
Table 79 - Table Properties
CIP Instance Number
816
PCCC File Number
N25
No. of Elements
30
Length in Words
30
Data Type
Int16
Data Access
Read/Write
Table 80 - Configuration.OptionalComm.DNT Data Table
Element Number
Type
Tag Name
Description
Default
Range
0
Int16
DeviceNet_Address
DeviceNet optional card device address
63
0…63
1
Int16
DeviceNet_Baudrate
DeviceNet optional card communication rate.
0 - 125k
1 - 250k
2 - 500k
3 - AutoBaud
3
0…3
2…29
Int16
Reserved
Future Use
0
0