Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

209

Communication

Chapter 9

6.

Complete the New Module setup as shown in the example and click OK
when done.

7.

In the Module Properties dialog box, click the Connection tab and choose
a Requested Packet Interval to suit your application.

The fastest metering update rate in the PowerMonitor 5000 unit is once
per cycle, which is 20 ms for 50 Hz and 16.67 ms for 60 Hz.

8.

Click OK when done.

9.

Download the revised program to the Logix controller.

You can leave the controller in Remote Program mode for now.

TIP

The Comm. Format, Input, Output, and Configuration assembly
instances and sizes must be entered as shown. Name and optional
Description are your choice. Node is the ControlNet address of the
power monitor. Click OK when done.