Powerquality.harmonics_results (m6 model) – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 355

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

355

PowerMonitor 5000 Unit Data Tables

Appendix A

PowerQuality.Harmonics_Results (M6 model)

Table 179 - Table Properties

CIP Instance Number

860

PCCC File Number

F69

No. of Elements

37

Length in Words

74

Data Type

Real

Data Access

Read Only

Table 180 - PowerQuality.Harmonics_Results Data Table

Element
Number

Type

Tag Name

Description

Units

Range

0

Real

Metering_Date_Sta
mp

Date of cycle collection MM:DD:YY

MMDDYY

0…123199

1

Real

Metering_Time_Sta
mp

Time of cycle collection hhmmss

hhmmss

0…235959

2

Real

Metering_Microseco
nd_Stamp

Microsecond of cycle collection

uS

0.000…999999

3

Real

Channel

Indicates the channel selected in the most recent write of Table
Configuration.Harmonics_Optional_Read
0 = No Selection

1 = V1-N RMS

2 = V2-N RMS

3 = V3-N

4 = VN-G RMS

5 = V1-V2 RMS

6 = V2-V3 RMS

7 = V3-V1 RMS

8 = I1 RMS

9 = I2 RMS

10 = I3 RMS

11 = I4 RMS

12 = L1 kW RMS

13 = L2 kW RMS

14 = L3 kW RMS

15 = L1 kVAR RMS

16 = L2 kVAR RMS

17 = L3 kVAR RMS

18 = L1 kVA RMS

19 = L2 kVA RMS

20 = L3 kVA RMS

21 = Total kW RMS

22 = Total kVAR RMS

23 = Total kVA RMS

24 = V1-N Angle

25 = V2-N Angle

26 = V3-N Angle

27 = VN-G Angle

28 = V1-V2 Angle

29 = V2-V3 Angle

30 = V3-V1 Angle

31 = I1 Angle

32 = I2 Angle

33 = I3 Angl

34 = I4 Angle

1…34

4

Real

Order

Selected harmonics order range.
0 = DC…31st
1 = 32nd…63rd

0…1

(M6)