Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 236

Advertising
background image

236

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

100

2

INT

R1PulseDuration

Set as 50…1000 to indicate the duration of the pulse in milliseconds,
or set to 0 for KYZ-style transition output. (Toggle)
IMPORTANT: The value for delay is rounded off to the nearest 10 ms
internally during this function.

Relay 1 Output
Duration

0 or 50…1000

2

INT

Pad23

For alignment purpose

104

1

SINT

R2OutputMode

The parameter selected will pulse the relay 2 output at a rate that
equals the parameter value divided by relay 2 scale.
0 = Setpoint Control
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah

Relay 2 Output
Parameter

0…6

1

SINT

Pad24

For alignment purpose

2

INT

Pad25

For alignment purpose

108

4

DINT

R2PulseScale

The relay 2 output parameter divided by the relay 2 scale is the output
pulse rate. Example: Wh is selected for the parameter and 1,000 is the
scale value. The output is pulsed every kWh.

Relay 2 Output
Scale

1…100,000

112

2

INT

R2PulseDuration

Set as 50…1000 to indicate the duration of the pulse in milliseconds,
or set to 0 for KYZ-style transition output. (Toggle)
IMPORTANT: The value for delay is rounded off to the nearest 10 ms
internally during this function.

Relay 2 Output
Duration

0 or 50…1000

2

INT

Pad26

For alignment purpose

116

1

SINT

R2OutputMode

The parameter selected will pulse the relay 3 output at a rate that
equals the parameter value divided by relay 3 scale.
0 = Setpoint Control
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah

Relay 3 Output
Parameter

0…6

1

SINT

Pad27

For alignment purpose

2

INT

Pad28

For alignment purpose

120

4

DINT

R3PulseScale

The relay 3 output parameter divided by the relay 3 scale is the output
pulse rate. Example: Wh is selected for the parameter and 1,000 is the
scale value. The output is pulsed every kWh.

Relay 3 Output
Scale

1…100,000

124

4

INT

R3PulseDuration

Set as 50…1000 to indicate the duration of the pulse in milliseconds,
or set to 0 for KYZ-style transition output. (Toggle)
IMPORTANT: The value for delay is rounded off to the nearest 10 ms
internally during this function.

Relay 3 Output
Duration

0 or 50…1000

2

INT

Pad29

For alignment purpose

128

4

DINT

S1ScaleFactor

When a status pulse is received the count is increased by the scale
factor. (Input pulse * input scale) added to total status count.

Status 1 Input
Scaling

1…1,000,000

132

4

DINT

S2ScaleFactor

When a status pulse is received the count is increased by the scale
factor. (Input pulse * input scale) added to total status count.

Status 2 Input
Scaling

1…1,000,000

136

4

DINT

S3ScaleFactor

When a status pulse is received the count is increased by the scale
factor. (Input pulse * input scale) added to total status count.

Status 3 Input
Scaling

1…1,000,000

140

4

DINT

S4ScaleFactor

When a status pulse is received the count is increased by the scale
factor. (Input pulse * input scale) added to total status count.

Status 4 Input
Scaling

1…1,000,000

Table 44 - Configuration.Instance Data Table