Install the PowerMonitor 5000 Unit

Chapter 2

Control Power

Connect the PowerMonitor 5000 unit to a source of 120/240V AC (or 24V DC,
shown with dashed lines) control power through a user-provided disconnecting
means, such as a switch or circuit breaker close to the power monitor. Provide
overcurrent protection sized to protect the wiring, for example, a 5 A rated fuse.
Overcurrent protection is included in the 1400-PM-ACC accessory kit. The
PowerMonitor 5000 unit is internally protected. Apply control power only after
all wiring connections are made to the unit.

Figure 18 - Control Power

Connect Communication

This section describes how to connect communication networks.

USB Communication

The USB Device port can be used to set-up a temporary, point-to-point
connection between a personal computer and the PowerMonitor 5000 unit. This
connection is used for configuration, data monitoring, diagnostics, and
maintenance by using the unit's built-in web pages. The USB Device port is a
standard USB Mini-B receptacle. You need to install drivers to enable USB
communication.

To connect your personal computer to the PowerMonitor 5000 unit, use a
standard USB cable with a Type-A and Mini-B male plugs, Allen-Bradley catalog
number 2711C-CBL-UU02 or equivalent.

*

*

*

*

L1

L2

GND

24V

com

Ground

24V DC

120/240V AC 50/60 Hz,
or 120/ 240V DC

* Provided by user.

TIP

You can also display the PowerMonitor 5000 web interface by using a
PanelView Plus 6 terminal with a 2711P-RP9_ logic module with extended
features. USB communication drivers are already installed in the logic module.

Refer to

Configure the Connection on page 34

to continue the setup.