Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 153

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

153

Logic Functions

Chapter 7

KYZ_Solid_State_Output_Scale
Output_Relay_1_Output_Scale
Output_Relay_2_Output_Scale
Output_Relay_3_Output_Scale

The output parameter divided by the scale is the output pulse rate. Example: Wh
is selected for the parameter and 1,000 is the scale value. The output is pulsed
every 1000 Wh, or 1 kWh. This parameter is ignored for setpoint or
communication operation.

KYZ_Pulse_Duration_Setting
Output_Relay_1_Pulse_Duration_Setting
Output_Relay_2_Pulse_Duration_Setting
Output_Relay_3_Pulse_Duration_Setting

Defines the duration of each output pulse. These are the choices:

0 = KYZ-style transition output (toggle)

50…1000 = Pulse duration in milliseconds, rounded to the nearest 10 ms.
This parameter is ignored for setpoint or communication operation.

Default_KYZ_State_On_Comm_Loss
Default_Relay_1_State_On_Comm_Loss
Default_Relay_2_State_On_Comm_Loss
Default_Relay_3_State_On_Comm_Loss

In Class 1 scheduled communication operation, this parameter defines the
behavior of the specified output if the power monitor experiences a
communication loss/communication recovery. These are the selections:

0 = Last state/resume
1 = Last state/freeze
2 = De-energize/resume
3 = De-energize/freeze
4 = Local control