Configuration.setpoint_logic (m6 model), Configuration.setpoint_logic data table – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 266

Advertising
background image

266

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

Configuration.Setpoint_Logic (M6 Model)

Table 69 - Table Properties

CIP Instance Number

811

PCCC File Number

N20

No. of Elements

100

Length in Words

100

Data Type

Int16

Data Access

Read/Write

Table 70 - Configuration.Setpoint_Logic Data Table

Element
Number

Type

Tag Name

Description

Default

Range

0

Int16

Logic Level 1
Gate 1 Function

Selects the logic type
0 = disabled
1 = AND
2 = NAND
3 = OR
4 = NOR
5 = XOR
6 = XNOR
IMPORTANT: XOR and XNOR use Inputs 1 and 2 only.

0

0…6

1

Int16

L1_G1 Input 1

Selects the first input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3

20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.

0

-20…20

2

Int16

L1_G1 Input 2

Selects the second input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3

20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.

0

-20…20

3

Int16

L1_G1 Input 3

Selects the third input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3

20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.

0

-20…20

4

Int16

L1_G1 Input 4

Selects the fourth input parameter for the gate. Each gate has four inputs.
0 = Disabled
1= Setpoint 1
2 = Setpoint 2
3 = Setpoint 3

20 = Setpoint 20 IMPORTANT: Negative numbers invert the input.

0

-20…20