Statistics.logging – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 320

Advertising
background image

320

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

Statistics.Logging

Table 125 - Table Properties

CIP Instance Number

833

PCCC File Number

N42

No. of Elements

20

Length in Words

20

Data Type

Int16

Data Access

Read Only

Table 126 - Statistics.Logging Data Table

Element
Number

Type

Tag Name

Description

Range

0

Int16

Number of Unit Event Log Records

On a read of this table the value of this parameter is the number of Unit Event Records
available. This log is returned only by using the incremental return method.

0…100

1

Int16

Number of Time of Use Log Records

On a read of this table the value of this parameter is the number of Time of Use Log
Records available. 1 is the current record being updated before logging.

0…13

2

Int16

Number of Load Factor Log Records

On a read of this table the value of this parameter is the number of Load Factor Log
Records available. 1 is the current record being updated before logging.

0…13

3

Int16

Number of Setpoint Records

On a read of this table the value of this parameter is the number of setpoint event records
available.

0…100

4

Int16

Number of Alarm Records

On a read of this table the value of this parameter is the number of Alarm event records
available.

0…100

5

Int16

Number of Energy Log Records x1000

On a read of this table the value of this parameter is the x1000 number of Energy Log
Records available.

0…30,000

6

Int16

Number of Energy Log Records x1

On a read of this table the value of this parameter is the x1 number of Energy Log Records
available.

0…999

7

Int16

Number of Data Log Records x1000

On a read of this table the value of this parameter is the x1000 number of data log records
available.

0…30,000

8

Int16

Number of Data Log Records x1

On a read of this table the value of this parameter is the x1 number of data log records
available.

0…999

9

Int16

Number of Data Log Files

Total Data Log files that have been saved

0…256

10

Int16

Number of Energy Log Files

Total Energy Log files that have been saved

0…256

11

Int16

Number of Trigger Data Records

On a read of this table the value of this parameter is the number of Trigger data records
available.

0…3600

12

Int16

Number of Trigger Data Files

Total trigger data files have been saved

0…60

13

Int16

Number of Waveform Cycles

On a read of this table the value of this parameter is the number of waveform data cycles
available.

0…21600

14

Int16

Number of Waveform Files

Total waveform files have been saved

0…256

15

Int16

Number of Power Quality Records

On a read of this table the value of this parameter is the number of power quality records
available.

0…100

16…19

Int16

Reserved

Reserved for future use.

0