Use an URC

Because every remote device needs power, you will have to add external power supply every three
remotes devices or every 300 meters. Except for the first three remote devices or the first 300m,
power will be delivered by the UAPG2. The maximum distance between UAPG2 and remote device is
800m.

There are six main steps to configure a (or several) URC(s):
1) Connect the URC
2) Define the system with the URC
3) Search and set the URC (The UAPG2 scans the system and attributes a specific IP address for each

remotes device (PPM and URC) automatically)

4) Define and adjust URC's parameters
5) Assign adjustments
6) Set adjustments

Note: If you have some troubles during the procedure, try to clean the UAPG2 memory (first try to
clear remote IP address, after, if needed, try to clean MCU data then restart UAPG2-PPM
software)

Connect URC

To connect URC, use the RS485 connector at the rear of the UAPG2. For several URCs you may
have to use Junction boxes (JB), or you can daisy-chain them.

Note: It is recommended to not put more than 8 remote devices (PPM and/or URC) on one UAPG2.

Note: If you have a bad connection: Switch on the end line resistor on the last URC (Blue switch: 1 =
inactive, White square = active).

Define the system with URC

Drag and drop the URC to the communication port of the UAPG2 (C, at the top of the inputs). If you
have several URCs and several UAPG2, define the URC to the UAPG2 in the same way as the
physical connection.