E94AYCCA communication manual (CANopen®)

Parameter reference

Communication-relevant parameters of the standard device

106

L

EDS94AYCCA EN 5.0 - 06/2012

C01130

Parameter | Name:

C01130 | CAN SYNC application cycle

Data type: UNSIGNED_16

Index: 23445

d

= 5B95

h

From software version V3.0

This parameter influences the effect of the sync phase position (

C01122

) with regard to the instant of acceptance

of the synchronous PDOs by the application or the instant of transmission of the synchronous PDOs to the system

bus (CANopen).

• The resulting PDO delay can be calculated with the following formula, taking an internal processing time of

150 μs into consideration: PDO delay = (

C01121

-

C01122

+ 150 μs) modulo C01130

• For the Lenze setting, the behaviour remains as before; the sync phase position (

C01122

) is always calculated

"modulo 1000".

• The set value is automatically rounded down to multiples of 1000 μs.



Effect of C01130 on the sync phase position ( 54)

Note: Setting the application cycle to a higher value than the sync cycle time (

C01121

) results in an undefined

response. The same applies if the value set for the sync phase position (

C01122

) is higher than the sync cycle time

(

C01121

). In this case, the drive usually cannot send synchronous PDOs on the system bus anymore.



Synchronisation of PDOs via sync telegram ( 50)

Setting range

(min. value | unit | max. value)

Lenze setting

1000

μs

65000 1000 μs

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1

Note!

The standard device codes C01501 and C01502 are not effective when using the

CANopen communication module.