Segment cable length
The segment cable length is determined by the cable cross-section used and by the number

of nodes. Repeaters divide the total cable length into segments. If no repeaters are used,

the segment cable length is identical to the total cable length.

Example: selection help

Max. number of

nodes per segment

Cable cross-section (can be interpolated)

0.25 mm

2

(AWG 24)

0.50 mm

2

(AWG 21)

0.75 mm

2

(AWG 19)

1.00 mm

2

(AWG 18)

2

240 m

430 m

650 m

940 m

5

230 m

420 m

640 m

920 m

10

230 m

410 m

620 m

900 m

20

210 m

390 m

580 m

850 m

32

200 m

360 m

550 m

800 m

63

170 m

310 m

470 m

690 m

100

150 m

270 m

410 m

600 m

Given
Total cable length to be

implemented

200 m

Number of nodes

63

Results
Max. possible baud rate

250 kbps

(derived from table

Total cable length ( 28)

)

Cable cross-section required

(interpolated)

0.30 mm

2

(AWG23)

(derived from the table

Segment cable length ( 29)

)

Cable cross-section of standard CAN

cable

0.34 mm

2

(AWG22)



Specification of the bus cable ( 27)