E94AYCCA communication manual (CANopen®)

Parameter reference

Parameters of the communication module for slot MXI2

132

L

EDS94AYCCA EN 5.0 - 06/2012

C14323

C14324

C14343

Parameter | Name:

C14323 | CAN RPDOx Rx mode

Data type: UNSIGNED_8

Index: 11252

d

= 2BF4

h

RPDO transmission type according to DS301, V4.02

• For the RPDO serves as monitoring setting in the case of sync-controlled PDOs.

• Types 0 (acyclic sync), 1-240 (cyclic sync), 254 (event-controlled manufacturer-specific), 255 (event-controlled

device-profile-specific) are supported.

• The basic PDO setting is "254" (event-controlled).

• Mapping of the CANopen objects

I-1400/2

...

I-1403/2

(see DS301, V4.02).



Transmission type ( 47)

Setting range

(min. value | unit | max. value)

0

255

Subcodes

Lenze setting

Information

C14323/1

254

Transmission mode for RPDO1 ... RPDO4

...
C14323/4

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1

Parameter | Name:

C14324 | CAN TPDOx delay time

Data type: UNSIGNED_16

Index: 11251

d

= 2BF3

h

TPDO inhibit time according to DS301, V4.02

• Minimum time between the transmission of two identical TPDOs.

• The time is entered in 1/10 ms and automatically rounded to full milliseconds by the code.

• Mapping of the CANopen objects

I-1800/3

...

I-1803/3

(see DS301, V4.02).

Setting range

(min. value | unit | max. value)

0

1/10 ms

65535

Subcodes

Lenze setting

Information

C14324/1

0 1/10 ms

Delay time for TPDO1 ... TPDO4

...
C14324/4

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1

Parameter | Name:

C14343 | CAN TPDO counter

Data type: UNSIGNED_32

Index: 11232

d

= 2BE0

h

Counter for TPDO1 ... TPDO4
Display range

(min. value | unit | max. value)

0

4294967295

Subcodes

Information

C14343/1
...
C14343/4

;

Read access … Write access … CINH … PLC STOP … No transfer

Scaling factor: 1