E94AYCCA communication manual (CANopen®)

Error messages

Possible causes and remedies

CAN module (MXI1): emergency configuration faulty [0x009f0000]

CAN module (MXI1): node guarding error 1 ... 32 [0x00a00000 ... 0x00a0001f]

CAN module (MXI1): NMT master configuration faulty [0x00a00020]

CAN module (MXI1) RPDO1: telegram not received or faulty [0x00a10000]

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

CANopen communication module in MXI1: CAN

emergency configuration is faulty.

• Faulty download of an »Engineer« or »PLC Designer«

project.

• Invalid CAN settings according to DS301, V4.02

carried out in the »Engineer« or »PLC Designer«

project.

• Repeat download

• Correct CAN settings in the project and have project

regenerated.

Response (Lenze setting printed in bold)

Setting:

C13612/1...32

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI1: cyclic node

monitoring

• The CAN master has not received a response to a node

guarding telegram (RTR) by the node 1 ... 32 within

the time defined.

• Reactivate CAN node by mains switching, restart of

the controller (C00002 = 11000) or "Reset node"

(C00002 = 92).

• Parameterise node guarding monitoring time again

or switch off the monitoring.

• Reset possibly active error status.

Tip: Before switching the mains and restarting the

controller, save the current parameter set (C00002 = 11).



Node guarding protocol ( 74)

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

CANopen communication module in MXI1: on the CAN

master a configuration error has occurred in the network

management.

• Faulty download of an »Engineer« or »PLC Designer«

project.

• Invalid CAN settings according to DS301, V4.02

carried out in the »Engineer« or »PLC Designer«

project.

• Node guarding or heartbeat parameterised

incorrectly.

• Repeat download

• Correct CAN settings in the project and have project

regenerated.

Response (Lenze setting printed in bold)

Setting:

C13591/1

/

C14591/1

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI1: CAN-IN1

error

• PDO telegram length incorrect.

• Error during transmission.

• PDO time monitoring has been triggered.

• Set correct telegram length for the CAN master

(transmitter).

• Eliminate fault in the ambience (e. g. EMC).

• Set different time monitoring or switch off time

monitoring.