Process data transfer

Transmission type

8.2

Transmission type

The process data objects are transmitted in an event-controlled or time-controlled way.

Event-controlled: The PDO is sent if a special device-internal event has occurred, for

instance, when the data contents of the TPDO have changed or when a transmission

cycle time has elapsed.

Synchronous: A TPDO (or RPDO) is transmitted (or received) after the device has

received a sync telegram (with identifier 0x80).

Cyclically: The PDOs are transmitted in fixed time intervals after the transmission cycle

time has elapsed.

The table shows that combinations of logic operations (AND, OR) are also possible between

the different transmission modes:

Transmission type

PDO transmission

Logic operation

cyclic

synchronous

event-controlled

0

z

z

AND

1 ... 240

z

-

254, 255

z

z

OR

Transmission type

Description

0

The PDO is transmitted at every sync in an event-controlled manner (e. g. by means of a bit

change within the PDO).

1 ... 240

SYNC (with response)

• Selection n = 1: The PDO is transmitted with every sync.

• Selection 1 < n ≤ 240: The PDO is transmitted with every n-th sync.

254, 255

Event-controlled (with mask) with cyclic overlay

If this value is entered, the PDO transmission is event-controlled or cyclic.

(Note: The values "254" and "255" have the same meaning).

For cyclic overlay, a cycle time must be set for the respective PDO. In this case, cyclic

transmission takes place in addition to event-controlled transmission (e.g. through a bit

change in the PDO).