Emergency telegram

If the error status changes due to the occurrence or elimination of an internal device error,

an emergency telegram with the following structure is sent once to the NMT master:

Example

Tip!
A detailed description can be gathered from the CANopen specification DS301,

V4.02.

1st byte

2nd byte

3rd byte

4th byte

5th byte

6th byte

7th byte

8th byte

Emergency error code

Error register

Manufacturer-specific error message

Low byte

High byte

I-1001

0x00

(reserved)

Low word

High word

Low byte

High byte

Low byte

High byte

See table below

• With emergency error code "0x1000: Lenze error number"

(value displayed in C00168)

• With all other emergency error codes, the value "0" is entered

here.

Emergency error code

Error register

Cause

0x0000

0xxx

One of several errors eliminated

0x00

Single error eliminated (no more errors)

0x1000

0x01

Generic error

• In the standard device, an error has occurred with the error

response "Fault", "Trouble", "Quick stop by trouble", "Warning",

"Warning locked" or "System fault".

• Error message is the Lenze error number (C00168).

• For error cause see error description (C00166).

0x3100

0x01

Supply voltage of standard device faulty or failed

0x8100

0x11

Communication error (warning)

0x8130

0x11

Life guarding error or heartbeat error

0x8150

0x11

Collision of identifiers (COB-IDs): An identifier parameterised for

reception is also used for transmission.

0x8210

0x11

PDO length is shorter than the expected PDO length

0x8220

0x11

PDO length is longer than the expected PDO length

0x8700

0x11

Sync telegram monitoring

1st byte

2nd byte

3rd byte

4th byte

5th byte

6th byte

7th byte

8th byte

Emergency error code

Error register

Manufacturer-specific error message

0x00

0x10

0x01

0x00

(reserved)

0x1B

0x00

0x7B

0x00

Generic error

Lenze error message "0x007B001B: Encoder wire

breakage".

Corresponding "error-free" message: value

"0x00000000"