2 possible causes and remedies, Can module (mxi1): bus-off [0x009d0000, Possible causes and remedies – Lenze E94AYCCA User Manual

Page 91: 0x008c0017, 0x008c0018, 0x009d0000, 0x009d0001, E94aycca communication manual (canopen®), Error messages possible causes and remedies

Advertising
background image

EDS94AYCCA EN 5.0 - 06/2012

L

91

E94AYCCA communication manual (CANopen®)

Error messages

Possible causes and remedies

12.2

Possible causes and remedies

This chapter includes a list of all error messages of the communication module in

numerically ascending order of the error number. Possible causes and remedies as well as

responses to error messages are described in detail.



Short overview of the CANopen error messages

( 89)

MXI1: CAN module is missing or is incompatible [0x008c0017]

MXI2: CAN module is missing or is incompatible [0x008c0018]

CAN module (MXI1): bus-off [0x009d0000]

CAN module (MXI1): invalid node address 0 [0x009d0001]

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

The CANopen communication module in module slot

MXI1 is incompatible with the application.

Use a communication module supported by the

application.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

The CANopen communication module in module slot

MXI2 is incompatible with the application.

Use a communication module supported by the

application.

Response (Lenze setting printed in bold)

Setting:

C13595

(; Adjustable response)

;

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning : Information

Cause

Remedy

CANopen communication module in MXI1: "bus-off"

status

• Cable defect (e. g. loose contact)

• Too many faulty telegrams received.

• Two CAN nodes have the same node address.

• Eliminate fault in the ambience (e. g. EMC).

• Eliminate loose contact, tighten adapter.

• Assign different node addresses.



Setting the node address ( 33)

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble … Warning locked : Warning … Information

Cause

Remedy

CANopen communication module in MXI1: initialisation

error

• The hardware allocation of the node address was

selected via DIP switches and the DIP switches of the

node address are all set to "0".

• Instead of the impermissible node address 0, node

address 1 is used.

• Set a different node address than "0" and carry out

mains switching.



Setting the node address ( 33)