EDS94AYCCA EN 5.0 - 06/2012

L

87

E94AYCCA communication manual (CANopen®)

Diagnostics

LED status displays

Status displays BS and BE (connection status to the system bus (CANopen))

LEDs

Description

E94YCCA001D

BS

(green)

CANopen status

BE

(red)

CANopen error

LED status display

Meaning

BS (green)

BE (red)

CANopen status

CANopen error

BE lit only

-

Bus off

BS and BE flickering

Automatic detection of the baud rate is active.

BS blinking every 0.2 s | BE is off

Pre-operational

-

BS blinking every 0.2 s | BE blinking once, 1 s off

Warning limit reached

BS blinking every 0.2 s | BE blinking twice, 1 s off

Node guard event

BS lit only

Operational

-

BS lit | BE blinking once, 1 s off

Warning limit reached

BS lit | BE blinking twice, 1 s off

Node guard event

BS lit | BE blinking three times, 1 s off

Sync message error

BS blinking every 1 s | BE is off

Stopped

-

BS blinking every 1 s | BE blinking once, 1 s off

Warning limit reached

BS blinking every 1 s | BE blinking twice, 1 s off

Node guard event