0x00af0000, 0x00af001f, 0x00af0020 – Lenze E94AYCCA User Manual

Page 98: 0x00b00000, 0x00b00001, E94aycca communication manual (canopen®), Error messages possible causes and remedies

Advertising
background image

E94AYCCA communication manual (CANopen®)

Error messages

Possible causes and remedies

98

L

EDS94AYCCA EN 5.0 - 06/2012

CAN module (MXI2): node guarding error 1 ... 32 [0x00af0000 ... 0x00af001f]

CAN module (MXI2): NMT master configuration faulty [0x00af0020]

CAN module (MXI2) RPDO1: telegram not received or faulty [0x00b00000]

CAN module (MXI2) RPDO2: telegram not received or faulty [0x00b00001]

Response (Lenze setting printed in bold)

Setting:

C14612/1...32

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI2: cyclic node

monitoring

• The CAN master has not received a response to a node

guarding telegram (RTR) by the node 1 ... 32 within

the time defined.

• Reactivate CAN node by mains switching, restart of

the controller (C00002 = 11000) or "Reset node"

(C00002 = 92).

• Parameterise node guarding monitoring time again

or switch off the monitoring.

• Reset possibly active error status.

Tip: Before switching the mains and restarting the

controller, save the current parameter set (C00002 = 11).



Node guarding protocol ( 74)

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

CANopen communication module in MXI2: on the CAN

master a configuration error has occurred in the network

management.

• Faulty download of an »Engineer« or »PLC Designer«

project.

• Invalid CAN settings according to DS301, V4.02

carried out in the »Engineer« or »PLC Designer«

project.

• Node guarding or heartbeat parameterised

incorrectly.

• Repeat download

• Correct CAN settings in the project and have project

regenerated.

Response (Lenze setting printed in bold)

Setting:

C14591/1

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI2: CAN-IN1

error

• PDO telegram length incorrect.

• Error during transmission.

• PDO time monitoring has been triggered.

• Set correct telegram length for the CAN master

(transmitter).

• Eliminate fault in the ambience (e. g. EMC).

• Set different time monitoring or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C14591/2

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI2: CAN-IN2

error

• PDO telegram length incorrect.

• Error during transmission.

• PDO time monitoring has been triggered.

• Set correct telegram length for the CAN master

(transmitter).

• Eliminate fault in the ambience (e. g. EMC).

• Set different time monitoring or switch off time

monitoring.