I-1003 - Pre-defined error field

Error history
This object indicates that an error has occurred in the communication module and in the

standard device.

Index:

I-1003

Name:

Pre-defined error field

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Number of errors

0

0

255 rw

U8

1 ... 10: Standard error field

-

0

4294967295 ro

U32

Subindex

Meaning

0

Number of the error messages stored

1 ... 10

Display of the error list

The error messages (U32) consist of a 16-bit error code and a 16-bit manufacturer-

specific information field.

Note!

The values in the "standard error field" under subindexes 1 ... 10 will be deleted

if the subindex "number of recorded errors" is overwritten with the value "0".

Emergency

error code

Cause

Entry in the error

register

(

I-1001

)

0x0000

One of several errors eliminated

0xxx

Elimination of an individual error

(afterwards error-free state)

0x00

0x1000

Standard device is in error status (error response "Trouble",

"Message", "Warning", "Fault", "Quick stop by trouble" or "System

fault")

0x01

0x3100

Supply voltage of standard device faulty or failed

0x01

0x8100

Communication error (warning)

0x11

0x8130

Life guard error or heartbeat error

0x11

0x8150

Collision of COB-IDs: an ID parameterised for reception also is used

for transmission.

0x11

0x8210

PDO length is shorter than the expected PDO length

0x11

0x8220

PDO length is longer than the expected PDO length

0x11

0x8700

Sync telegram monitoring

0x11

Advertising