C13321

C13322

Parameter | Name:

C13321 | CAN RPDOx identifier

Data type: BITFIELD_32

Index: 11254

d

= 2BF6

h

Identifier for RPDO1 ... RPDO4

• If bit 31 is set (0x8nnnnnnn), the RPDO is deactivated.

• The basic setting is according to the "Predefined Connection Set".

• Mapping of the CANopen objects

I-1400/1

...

I-1403/1

(see DS301, V4.02).



Identifiers of the process data objects ( 46)

Setting range
0x00000000

0xFFFFFFFF

Value is bit-coded:

Information

Bit 0 COB-ID bit 0

• Bit 0 ... 10: COB-ID

• Bit 11 ... 30: Reserved

• Bit 31: PDO invalid

... ...

Bit 31 PDO invalid

Subcodes

Lenze setting

Information

C13321/1

0x00000201

Identifier RPDO1

• After changing the node address and executing

"Reset node" (C00002 = 92), here the value 0x200 +

node address is set by default.

C13321/2

0x00000301

Identifier RPDO2

• After changing the node address and executing

"Reset node" (C00002 = 92), here the value 0x300 +

node address is set by default.

C13321/3

0x00000401

Identifier RPDO3

• After changing the node address and executing

"Reset node" (C00002 = 92), here the value 0x400 +

node address is set by default.

C13321/4

0x00000501

Identifier RPDO4

• After changing the node address and executing

"Reset node" (C00002 = 92), here the value 0x500 +

node address is set by default.

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1

Parameter | Name:

C13322 | CAN TPDOx Tx mode

Data type: UNSIGNED_8

Index: 11253

d

= 2BF5

h

TPDO transmission type according to DS301, V4.02

• The types 0 (acyclic sync), 1-240 (cyclic sync), 254 (event-controlled manufacturer-specific), 255 (event-

controlled device-profile-specific) are supported.

• The basic setting for all PDOs is the event-controlled setting "254".

• Mapping of the CANopen objects

I-1800/2

...

I-1803/2

(see DS301, V4.02).



Transmission type ( 47)

Setting range

(min. value | unit | max. value)

0

255

Subcodes

Lenze setting

Information

C13322/1

254

Transmission mode for TPDO1 ... TPDO4

...
C13322/4

;

Read access ; Write access … CINH … PLC STOP … No transfer