Can module (mxi1): life guarding error [0x009e0020, 0x009d0002, 0x009e0000 – Lenze E94AYCCA User Manual

Page 92: 0x009e0020, 0x009e0021, E94aycca communication manual (canopen®), Error messages possible causes and remedies

Advertising
background image

E94AYCCA communication manual (CANopen®)

Error messages

Possible causes and remedies

92

L

EDS94AYCCA EN 5.0 - 06/2012

CAN module (MXI1): basic configuration invalid [0x009d0002]

CAN module (MXI1): heartbeat error index 1 ... 32 [0x009e0000 ... 0x009e001f]

CAN module (MXI1): life guarding error [0x009e0020]

CAN module (MXI1): NMT slave configuration faulty [0x009e0021]

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

CANopen communication module in MXI1:

configuration error

• Faulty download of an »Engineer« or »PLC Designer«

project.

• Invalid CAN settings according to DS301, V4.02

carried out in the »Engineer« or »PLC Designer«

project.

• Repeat download

• Correct CAN settings in the project and have project

regenerated.

Response (Lenze setting printed in bold)

Setting:

C13613/1...32

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI1: cyclic node

monitoring

• The CAN node has not received a heartbeat telegram

from node 1 ... 32 within the time defined.

• Reactivate CAN node by mains switching, restart of

the controller (C00002 = 11000) or "Reset node"

(C00002 = 92).

• Parameterise heartbeat producer monitoring time

again or switch off monitoring.

• Reset possibly active error status.

Tip: Before switching the mains and restarting the

controller, save the current parameter set (C00002 = 11).



Heartbeat protocol ( 80)

Response (Lenze setting printed in bold)

Setting:

C13614

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI1: cyclic node

monitoring

• Slave response: The maximum time between two

node guarding telegrams (RTR) from the master has

been exceeded.

Parameterise life guarding monitoring time again or

switch it off.



Node guarding protocol ( 74)

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

CANopen communication module in MXI1: on the CAN

slave a configuration error has occurred in the network

management.

• Faulty download of an »Engineer« or »PLC Designer«

project.

• Invalid CAN settings according to DS301, V4.02

carried out in the »Engineer« or »PLC Designer«

project.

• Node guarding or heartbeat parameterised

incorrectly.

• Repeat download

• Correct CAN settings in the project and have project

regenerated.