C13367 | can sync rx identifier, C13368 | can sync tx identifier, C13372 | can sdo server rx identifier – Lenze E94AYCCA User Manual

Page 117: C13367, C13368, C13372, E94aycca communication manual (canopen®)

Advertising
background image

EDS94AYCCA EN 5.0 - 06/2012

L

117

E94AYCCA communication manual (CANopen®)

Parameter reference

Parameters of the communication module for slot MXI1

C13367

C13368

C13372

Parameter | Name:

C13367 | CAN sync Rx identifier

Data type: UNSIGNED_32

Index: 11208

d

= 2BC8

h

Identifier with which the sync slave is to receive sync telegrams.

• Mapping of the CANopen object

I-1005

(see DS301, V4.02).



Synchronisation of PDOs via sync telegram ( 50)

Setting range

(min. value | unit | max. value)

Lenze setting

0

2047 128

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1

Parameter | Name:

C13368 | CAN sync Tx identifier

Data type: UNSIGNED_32

Index: 11207

d

= 2BC7

h

Identifier with which the sync master is to send sync telegrams.

• Mapping of the CANopen object

I-1005

(see DS301, V4.02).



Synchronisation of PDOs via sync telegram ( 50)

Setting range

(min. value | unit | max. value)

Lenze setting

0

2047 128

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1

Parameter | Name:

C13372 | CAN SDO server Rx identifier

Data type: BITFIELD_32

Index: 11203

d

= 2BC3

h

Identifier with which the corresponding SDO server can be reached.

• If bit 31 is set (0x8nnnnnnn), the corresponding SDO server is deactivated.

• Mapping of the CANopen objects

I-1200/1

...

I-1209/1

(see DS301, V4.02).



Identifiers of the parameter data objects ( 62)

Setting range
0x00000000

0xFFFFFFFF

Value is bit-coded:

Information

Bit 0 COB-ID bit 0

• Bit 0 ... 10: COB-ID

• Bit 11 ... 30: Reserved

• Bit 31: SDO invalid

... ...

Bit 31 SDO invalid

Subcodes

Lenze setting

Information

C13372/1

0x00000601

SDO server channel 1 RX

• Subcode 1 contains the basic SDO channel. According

to DS301, V4.02 it can neither be changed nor

deactivated. Writing this subcode has no effect.

• The value in subcode 1 results from the node address

(

C13350

) + 0x600.

C13372/2

0x80000000

SDO server channel 2 RX

...

...

...

C13372/10

0x80000000

SDO server channel 10 RX

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1