Implemented CANopen objects

I-1800 - TPDO1 communication parameter

Communication parameter for the transmission of process data via TPDO1

[14-17] Data telegram assignment

How to change the identifier:

1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").

Index:

I-1800

Name:

TPDO1 communication parameter

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: highest subindex supported

5

- (only read access)

ro

U8

1: COB-ID used by TPDO

0x180 + node ID

0

4294967295 rw

U32

2: transmission type

254

0

255 rw

U8

3: inhibit time

0 ms

0

0.1 ms

65535 rw

U16

4: reserved

-

- (reserved, write or read access results in error

message 0x06090011)

rw

U8

5: event timer

0 ms

0

ms

65535 rw

U16

Subindex

Meaning

Lenze code

1

Identifier TPDO1

• The basic setting is according to the "Predefined

Connection Set": Identifier = 0x180 + node ID

C13320/1

/

C14320/1

2

TPDO transmission type according to DS301, V4.02



Transmission type ( 47)

C13322/1

/

C14322/1

3

Minimum time between the transmission of two

identical TPDOs (see DS301, V4.02).

C13324/1

/

C14324/1

5

Cycle time with which the PDOs are transmitted with the

transmission type "254".

C13356/1

/

C14356/1

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31

Bit 30

Bit 29 ... bit 11

Bit 10 ... bit 0

0/1

0/1

Extended identifier*

11-bit identifier

* The extended identifier is not supported - bit 11 ... bit 29 must be set to "0".

Bit

Setting

Bit 30

0 RTR to this PDO possible (Lenze).
1 RTR to this PDO not possible (cannot be set).

Bit 31

0 PDO active.
1 PDO inactive.