E94AYCCA communication manual (CANopen®)

Parameter reference

Parameters of the communication module for slot MXI2

136

L

EDS94AYCCA EN 5.0 - 06/2012

C14356

C14357

C14359

Parameter | Name:

C14356 | CAN TPDOx cycle time

Data type: UNSIGNED_16

Index: 11219

d

= 2BD3

h

TPDO event time according to DS301, V4.02

• If a different value than "0" is entered, the TPDO is transmitted without further consideration of the transport

type after the time set has elapsed.

• Mapping of the CANopen objects

I-1800/5

...

I-1803/5

(see DS301, 4.02).

Setting range

(min. value | unit | max. value)

0

ms

65535

Subcodes

Lenze setting

Information

C14356/1

0 ms

Cycle time for TPDO1 ... TPDO4

...
C14356/4

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1

Parameter | Name:

C14357 | CAN RPDOx monitoring time

Data type: UNSIGNED_16

Index: 11218

d

= 2BD2

h

Mapping of the RPDO event time (see DS301, V4.02)

• If a different value than "0" is entered, the RPDO is expected after the time set has elapsed.

• If the RPDO is not received within the expected time, an error message parameterisable under

C14591/1...4

can

be triggered.

Setting range

(min. value | unit | max. value)

0

ms

65535

Subcodes

Lenze setting

Information

C14357/1

3000 ms

Monitoring time for RPDO1 ... RPDO4

...
C14357/4

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1

Parameter | Name:

C14359 | CAN status

Data type: UNSIGNED_8

Index: 11216

d

= 2BD0

h

Display of the current CAN network status
Selection list

(read only)

0 Operational
1 Pre-operational
4 Boot-up
5 Stopped
7 Reset
8 Initialisation
9 Unknown

10 Baud rate autom. detected

;

Read access … Write access … CINH … PLC STOP … No transfer

Scaling factor: 1