C13383 | can life time factor, C13385 | can heartbeat consumer time, C13383 – Lenze E94AYCCA User Manual

Page 121: Set life time factor, Et life time factor, C13385, C13385/1, E94aycca communication manual (canopen®)

Advertising
background image

EDS94AYCCA EN 5.0 - 06/2012

L

121

E94AYCCA communication manual (CANopen®)

Parameter reference

Parameters of the communication module for slot MXI1

C13383

C13385

Parameter | Name:

C13383 | CAN Life Time Factor

Data type: UNSIGNED_8

Index: 11192

d

= 2BB8

h

• The life time factor multiplied with the guard time (

C13382

) is the time within which a node guarding telegram

must have arrived.

• Mapping of the CANopen object

I-100D

(see DS301, V4.02).



Node guarding protocol ( 74)

Setting range

(min. value | unit | max. value)

Lenze setting

0

255 0

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1

Parameter | Name:

C13385 | CAN Heartbeat Consumer Time

Data type: BITFIELD_32

Index: 11190

d

= 2BB6

h

The 32 subcodes represent the nodes which are to be monitored via heartbeat.

• Each bit-coded subcode entry contains the expected heartbeat time and the node ID (node address) from which

the heartbeat telegram is expected.

• The parameterised time is rounded down to an integer multiple of 5 ms and must have a higher value than the

heartbeat producer time (

C13381

) of the node to be monitored.

• The response to a missing heartbeat telegram can be parameterised in

C13613

.

• Mapping of the CANopen object

I-1016

(see DS301, V4.02).



Heartbeat protocol ( 80)

Setting range
0x00000000

0xFFFFFFFF

Value is bit-coded:

Information

Bit 0 Heartbeat time bit 0

• Bit 0 ... 15: Heartbeat time

• Bit 16 ... 23: Node address

• Bit 24 ... 31: Reserved

... ...

Bit 31 Reserved

Subcodes

Lenze setting

Information

C13385/1

0x00000000

Monitoring entry 1 ... 32

...
C13385/32

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1