2 setting the baud rate, Setting the baud rate, E94aycca communication manual (canopen®) – Lenze E94AYCCA User Manual

Page 34

Advertising
background image

E94AYCCA communication manual (CANopen®)

Commissioning

Possible settings via DIP switches

34

L

EDS94AYCCA EN 5.0 - 06/2012

6.2.2

Setting the baud rate

 The baud rate can be set with the DIP switches a ... d or via the »Engineer« (code

C13351

/

C14351

).

 If several CAN nodes are interconnected, their baud rates must be identical.

Tip!
The baud rate resulting from the DIP switch setting applied at last mains power-up

is indicated under

C13349/2

/

C14349/2

.

Switch positions

Baud rate

d

c

b

a

OFF

ON

ON

OFF

10 kbps

OFF

ON

OFF

ON

20 kbps

OFF

OFF

ON

ON

50 kbps

OFF

OFF

ON

OFF

125 kbps

OFF

OFF

OFF

ON

250 kbps

OFF

OFF

OFF

OFF

500 kbps

ON

ON

ON

OFF

800 kbps

OFF

ON

OFF

OFF

1000 kbps

OFF

ON

ON

ON

Automatic detection