C13320 | can tpdox identifier, C13320/1, C13320/2 – Lenze E94AYCCA User Manual

Page 109: C13320/3, C13320/4, C13320, E94aycca communication manual (canopen®)

Advertising
background image

EDS94AYCCA EN 5.0 - 06/2012

L

109

E94AYCCA communication manual (CANopen®)

Parameter reference

Parameters of the communication module for slot MXI1

C13320

Parameter | Name:

C13320 | CAN TPDOx identifier

Data type: BITFIELD_32

Index: 11255

d

= 2BF7

h

Identifier for TPDO1 ... TPDO4

• If bit 31 is set (0x8nnnnnnn), the TPDO is deactivated.

• The basic setting is according to the "Predefined Connection Set".

• Mapping of the CANopen objects

I-1800/1

...

I-1803/1

(see DS301, V4.02).



Identifiers of the process data objects ( 46)

Setting range
0x00000000

0xFFFFFFFF

Value is bit-coded:

Information

Bit 0 COB-ID bit 0

• Bit 0 ... 10: COB-ID

• Bit 11 ... 30: Reserved

• Bit 31: PDO invalid

... ...

Bit 31 PDO invalid

Subcodes

Lenze setting

Information

C13320/1

0x00000181

Identifier TPDO1

• After changing the node address and executing

"Reset node" (C00002 = 92), here the value 0x180 +

node address is set by default.

C13320/2

0x00000281

Identifier TPDO2

• After changing the node address and executing

"Reset node" (C00002 = 92), here the value 0x280 +

node address is set by default.

C13320/3

0x00000381

Identifier TPDO3

• After changing the node address and executing

"Reset node" (C00002 = 92), here the value 0x380 +

node address is set by default.

C13320/4

0x00000481

Identifier TPDO4

• After changing the node address and executing

"Reset node" (C00002 = 92), here the value 0x480 +

node address is set by default.

;

Read access ; Write access … CINH … PLC STOP … No transfer

Scaling factor: 1