Chapter

8

Configure Your Controller for EtherNet/IP
Communication

Introduction

The SmartGuard controller (catalog number 1752-L24BBBE) offers EtherNet/
IP connectivity.

Multicast Connections

You can make only two connections to the SmartGuard controller at any one
time. It can be one input and one output, or two inputs or two outputs. Even
though the connections are multicast, once the two connections are made, no
other connections are accepted.

For example, you can have two controllers connected to one input connection on
the SmartGuard controller multicast input assembly, and this would consume the
two EtherNet/IP connections.

Topic

Page

Configure Target I/O in RSNetWorx for DeviceNet Software

126

Set Up Your Controller as a Slave by Using RSLogix 5000 Software Generic Profile

130

Configure Communication between a Standard PanelView Terminal and a
SmartGuard 600 Controller over an EtherNet/IP Network

132