Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual

Page 134

Advertising
background image

134

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

Chapter 8

Configure Your Controller for EtherNet/IP Communication

For input assemblies, the CIP message codes include the following:

Service: 0xE - Get Single Attribute

Class: 4

Instance: 100 or 101 (input 1 or input 2 respectively)

Attribute: 3

For output assemblies, the CIP message codes include the following:

Service: 0x10 - Set Single Attribute

Class: 4

Instance: 102 or 103 (output 1 or output 2 respectively)

Attribute: 3

This example shows a CIP message code that accesses Input Assembly 1 of the
SmartGuard controller.

The member field is always defined as 1.

1.

From the Service Code pull-down menu, choose the CIP service code.

2.

Type the class, instance, and attributes codes for the tag in order to access
the correct target I/O assemblies in the SmartGuard controller.

The maximum size of a single member tag defined in the PanelView terminal is a
DINT (4 bytes). A target I/O assembly in the SmartGuard controller can be as
large as 16 bytes. In order to access all of the bytes in the target assembly, you may
need to create up to 4 DINT tags, where an Offset is defined for each tag to
correspond with the target bytes of that tag.

Advertising
This manual is related to the following products: