Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

269

Explicit Messages

Appendix E

SV for Test
Output Total On
Time or Contact
Operation
Counter

Read

Reads the SV of the total on time
or contact operation counter for
the input (1…4) specified by the
Instance ID.

0E hex

35B hex

01…04 hex

86 hex

4 bytes
0000 0000 to
FFFF FFFF hex
(0 to 4,294,967,295)

Write

Writes the SV of the total on time
or contact operation counter for
the input (1…4) specified by the
Instance ID.

10 hex

35B hex

01…04 hex

86 hex

4 bytes
0000 0000…
FFFF FFFF hex
(0…
4,294,967,295)

Read Test Output
Total On Time or
Contact
Operation
Counter

Read

Reads the total on time or
contact operation counter for the
input (1…4) specified by the
Instance ID.

0E hex

35B hex

01…04 hex

84 hex

4 bytes
0000 0000…
FFFF FFFF hex
(0… 4,294,967,295)

Reset Test Output
Total On Time or
Contact
Operation
Counter

Reset

Resets to 0 the total on time or
contact operation counter for the
test output (1…4) specified by
the Instance ID.

05 hex

35B hex

01…04 hex

84 hex

Read Monitor
Status of Test
Output Total on
Time or Contact
Operation
Counter

Read

Reads the monitor status of the
total on time or contact
operation counter for the test
output (1…4) specified by the
Instance ID.

0E hex

35B hex

01…04 hex

85 hex

1 byte
00 hex: in range
01 hex: out of range (over
monitor value)

Read Test Output
Safety Flag

Read

Reads the normal flag status for
the test output (1…4) specified
by the Instance ID.

0E hex

35B hex

01…04 hex

68 hex

1 byte
00 hex: normal
01 hex: error

Read Test Output
Error Information
Cause

Read

Reads the cause for the normal
flag of the test output (1…4)
specified by the Instance ID being
off (error).

0E hex

35B hex

01…04 hex

76 hex

1 byte
00 hex: no error
01 hex: invalid
configuration
02 hex: overcurrent
detection
05 hex: high constant error
06 hex: undercurrent
detection

Read OR of Test
Output Safety
Flags

Read

Reads the logical OR of the
normal flag for all test outputs
(1…4).

0E hex

35C hex

01 hex

69 hex

1 byte
00 hex: all normal
01 hex: error

Read OR of
Monitor Status of
Test Output Total
On Times or
Contact
Operation
Counters

Read

Reads the logical OR of the
monitor status of the total on
time or contact operation counter
for all test outputs (1…4).

0E hex

35C hex

01 hex

72 hex

1 byte
00 hex: all in range
01 hex: test output out of
range (over monitor value)

Table 44 - Monitoring Test Output Terminals

Explicit
Message

Service

Function

Command

Response

Service
Code

Class
ID

Instance ID

Attribute
ID

Data Size