Installing and Wiring the SmartGuard 600 Controller
Chapter 2
If you choose to use a different communication rate, the length of the trunkline
and types of cable determine which communication rates your application can
support.
Table 3 - DeviceNet Communication Rates and Cable Lengths
Communication Rate Distance, max
Cumulative Drop
Line Length
Flat Cable
Thick Cable
Thin Cable
125 Kpbs
420 m (1378 ft)
500 m (1640 ft)
100 m (328 ft)
156 m (512 ft)
250 Kpbs
200 m (656 ft)
250 m (820 ft)
100 m (328 ft)
78 m (256 ft)
500 Kpbs
75 m (246 ft)
100 m (328 ft)
100 m (328 ft)
39 m (128 ft)