Appendix D

Function Blocks Command Reference

Safety Gate Monitoring Function Block Error Handling

A discrepancy error is generated when one of the inputs is not in its correct state
for longer than the discrepancy time. For example, in Dual Channel Equivalent
mode, both inputs must be active (on) within the discrepancy time or an error
occurs.

If two pairs of inputs are selected and a synchronization time is entered, both
pairs of inputs must be in the same state within the synchronization time or a
synchronization error occurs. The discrepancy time applies to both inputs of the
same input pair being in the same state within a given time, whereas the
synchronization time applies to both sets of input pairs being in the same state
within a given time.

Use this table to diagnose and reset a discrepancy error condition in the Safety
Gate Monitoring function block.

1

0

0

1

0

1

0

0

1

0

1

0

1

0

0

1

0

1

0

1

1

0

1

1

0

1

0

1

1

0

1

1

0

0

0

1

1

0

0

0

1

1

0

1

0

1

1

0

1

0

1

1

1

0

0

1

1

1

0

0

1

1

1

1

1

1

1

1

1

0

Table 18 - Truth Table for Dual Channel (2 Pairs) Safety Gate Monitoring Function Block

Dual Channel Equivalent (2 Pairs)

Dual Channel Complementary (2 Pairs)

Input 1

(NC)

Input 2

(NC)

Input 3

(NC)

Input 4

(NC)

Output

Enable

Input 1

(NC)

Input 2

(NC)

Input 3

(NC)

Input 4

(NC)

Output

Enable

Table 19 - Error Detection and Reset for Safety Gate Monitoring Function Block

Error Condition

Status When an Error Occurs

To Reset the Error Condition

Output Enable

Fault

Present

Error Output

When Function Test is Disabled

When Function Test is Enabled

Discrepancy Error at
Pair 1

OFF
(Safety State)

ON

Discrepancy Error
Pair 1: ON

Remove the cause of the error and then either
1. Make the inputs active and inactive

again.

(2)

2. Change the controller’s operating mode to

IDLE and back to RUN.

Remove the cause of the error and then make
the inputs active and inactive again (that is,
perform the safety gate test).

Discrepancy at Pair 2

Discrepancy Error
Pair 2: ON

Function Test Error

(1)

Function Test Error:
ON

Synchronization
Error

Synchronization Test
Error: ON

(1) Safety gate test was not performed normally between Function Test signals.

(2) If a Discrepancy Error occurs in one of the pairs when set to Dual Channel Equivalent (2 Pairs) or Dual Channel Complementary (2 Pairs), make input pairs 1 and 2 both inactive and then active.