Chapter 2

Installing and Wiring the SmartGuard 600 Controller

Set the Node Address

Set the node address before you mount the controller.

Use a small flathead screwdriver to set the node address by using the two rotary
switches on the front panel of the controller. Use care not to scratch the switches.
Values from 00…63 are valid. The default setting is 63.

Follow these steps to set the node address.

1.

Set the tens digit of the node address (decimal) by turning the left rotary
switch.

2.

Set the ones digit by turning the right rotary switch.

3.

To allow the node address to be set by using RSNetWorx for DeviceNet
software, set the rotary switches to a value from 64…99.

Setting the Communication
Rate

Set the communication rate before you mount the controller.

DeviceNet Communication

The default communication rate for a DeviceNet network is 125 Kbps.

IMPORTANT

Turn off power to the controller before setting the node address or
communication rate via the switches.

Do not change the switch settings while the power supply is on. The controller
will detect this as a change in the configuration and will switch to the ABORT
mode.

IMPORTANT

A node address duplication error will occur if the same node address is set for
more than one node.

IMPORTANT

Turn off power to the controller before setting the node address or
communication rate via the switches.

Do not change the switch settings while the power supply is on. The controller
will detect this as a change in the configuration and will switch to the ABORT
mode.