Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual

Page 268

Advertising
background image

268

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

Appendix E

Explicit Messages

Read Monitor
Status of Output
Total On Time or
Contact
Operation
Counter

Read

Reads the monitor status of
the total on time or contact
operation counter for the
output (1…8) specified by the
Instance ID.

0E hex

3B hex

01…08 hex

67 hex

1 byte
00 hex: in range
01 hex: out of range (over
monitor value)

Read Safety
Output Normal
Flag

Read

Reads the normal flag status of
the number (1…8) specified
by the Instance ID.

0E hex

3B hex

01…08 hex

05 hex

1 byte
00 hex: error
01 hex: normal

Read Safety
Output Error
Information
Cause

Read

Reads the cause for the normal
flag of the number (1…8)
specified by the Instance ID
being off (error).

0E hex

3B hex

01…08 hex

6E hex

1 byte
00 hex: no error
01 hex: invalid configuration
02 hex: overcurrent detection
03 hex: short-circuit detection
04 hex: high constant error
05 hex: error in either of dual
channels
06 hex: internal relay circuit
error
07 hex: relay error
08 hex: data error between
dual channel outputs
09 hex: detection of short-
circuit between wires

Read AND of
Safety Output
Normal Flags

Read

Reads the cause for the normal
flag of the number (1…8)
specified by the Instance ID
being off (error).

0E hex

3C hex

01 hex

05 hex

1 byte
00 hex: error
01 hex: all normal

Read OR of
Monitor Status of
Output Total On
Times or Contact
Operation
Counters

Read

Reads the logical OR of the
monitor status of the total on
time or contact operation
counter for all outputs 1…8.

0E hex

3C hex

01 hex

72 hex

1 byte
00 hex: all in range
01 hex: input out of range
(over monitor value)

Table 43 - Setting and Monitoring Safety Output Terminals

Explicit
Message

Service

Function

Command

Response

Service
Code

Class
ID

Instance ID

Attribute
ID

Data Size

Table 44 - Monitoring Test Output Terminals

Explicit
Message

Service

Function

Command

Response

Service
Code

Class
ID

Instance ID

Attribute
ID

Data Size

Monitor Mode for
Terminal
Maintenance
Information

Read

Reads the monitor mode of
maintenance information for the
test output (1…4) specified by
the Instance ID.

0E hex

35B hex

01…04 hex

83 hex

1 byte
00 hex: Total On Time
mode
01 hex: Contact Operation
Counter mode

Write

Writes the monitor mode of
maintenance information for the
test output (1…4) specified by
the Instance ID.

10 hex

35B hex

01…04 hex

83 hex

1 byte
00 hex: Total On
Time mode
01 hex: Contact
Operation Counter
mode

Advertising
This manual is related to the following products: