Chapter 12

Monitor Status and Handle Faults

Alphanumeric Display

The controller’s alphanumeric display provides DeviceNet error codes,
DeviceNet node address, and EtherNet/IP address information. Under normal
operating conditions, the display shows the node address of the module, 00…63
in decimal format. If the controller is operating in a standalone configuration
(not networked), the display shows ‘nd’. The display flashes when the controller is
self-testing, configuring, or in Idle mode. If a fault exists, the display alternates
between the error code and the node address where the error occurred. If a fatal
error has occurred, the display shows the error code only.

When the service switch is pressed, the display shows the controller’s safety-
configuration signature two digits at a time. The configuration signature can also
be viewed on the Safety tab of the Controller Properties dialog box in
RSNetWorx for DeviceNet software. You can use the configuration signature to
verify that the program and configuration of the controller has not been changed.

When the IP address display switch is pressed for 1 second or longer, the display
shows the EtherNet/IP address that is set. The error code ‘n4’ is displayed if an
error occurs in the EtherNet/IP configuration.

For a description of the combinations of the status indicators and alphanumeric
display codes, including corrective actions, see Appendix B.

Table 12 - Explanation of Display Operation

Status

Display

Normal conditions with
DeviceNet enabled

Operating mode: Run
Safety I/O communication: operating

The controller node
address.

Lit

Operating mode: Run
Safety I/O communication: not operating

Flashing

Operating mode: Self-testing, Configuring, or Idle

Flashing

Normal conditions with
DeviceNet disabled

Operating mode: Run

nd

Lit

Operating mode: Self-testing, Configuring, or Idle

Flashing

Error conditions

Critical error

Error code only

Lit

Abort

Error code only

Lit

Nonfatal error

Alternates between the error
code and the node address where
the error occurred.