Application and Configuration Examples

Introduction

Emergency Stop Application

This example shows a dual channel emergency stop switch with manual reset.

Figure 91 - Emergency Stop Wiring Diagram

Topic

Page

Emergency Stop Application

271

Safety Gate Application with Automatic Reset

273

Dual Zone Safety Gate Application Using Emergency Stop Switch with Manual Reset

274

Safety Mat Application

276

Light Curtain Application

279

V1

G1 T

0

T1

I1

I0

I3

I5

I2

I4

I6

I7

T2

T3

E1

S1

11 21

12 22

O1

O0

V2 G

2

O3 O5

O2 O4 O6

O7

E2

KM 1

KM 2

I9

I8

I1 1

I1 3

I1 0

I1 2

I1 4

I1 5

KM 1 - N C

KM 2 - N C

M

KM1

KM2

S2

E1 and E2: 24V dc Power Supplies
S1: Emergency Stop Switch
S2: Reset Switch (N.O. Contact)
KM1 and KM2: Contactors

Connect a 24V dc power supply to terminals V0 and G0, the power supply terminals for internal circuits.