Chapter 7

Configure Your Controller for DeviceNet Communication

Download the Device Configurations

Once you have configured the safety and standard I/O module parameters,
download the configuration to the modules. To do this in RSNetWorx for
DeviceNet software, from the Device menu, choose Download to Device.

Configure Safety I/O Connections

Safety I/O connections are used to exchange data automatically with the safety
slaves without user programming. To perform safety I/O communication with
other slaves, you must configure the connection to the SmartGuard controller.

1.

On the Safety Connections tab, right-click the I/O module and choose
Add Connections to display all of the available connections.

The Add Safety Connection dialog box lets you configure a connection.

2.

Select the desired connection by choosing the Connection Name.

3.

Select a type of connection, either Multicast (input connections only) or
Point-to-point (input or output connections).

4.

Click Configuration signature must match.

This selection will cause the SmartGuard controller to include the
configuration signature when connecting to the I/O module and the I/O