Edm function block fault present output setting, Edm function block parameter, Edm function block error handling – Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual

Page 237

Advertising
background image

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

237

Function Blocks Command Reference

Appendix D

Block Properties dialog box in the Logic Editor of RSNetWorx for DeviceNet
software.

EDM error

Output 2

EDM Function Block Fault Present Output Setting

The Fault Present output can also be used in programming. To enable this
output, check the Use Fault Present checkbox on the Out point tab of the
Function Block Properties dialog box.

EDM Function Block Parameter

Set this parameter for the EDM function block.

EDM Function Block Error Handling

Use this table to diagnose and reset a discrepancy error condition in the EDM
function block.

Table 26 - EDM Function Block Parameter

Parameter

Range

Default

EDM Feedback Maximum Time Delay (T

EDM

)

100…1000 ms in 10 ms increments

300 ms

Table 27 - Error Detection and Reset for EDM Function Block

Error

Condition

Status When an Error Occurs

To Reset the Error Condition

Output Enable

Fault

Present

Error Output

EDM Feedback
Error

OFF
(Safety State)

ON

EDM Error
Output: ON

Remove the cause of the error and turn
ON the safety input.