Wire output devices – Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual

Page 36

Advertising
background image

36

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

Chapter 2

Installing and Wiring the SmartGuard 600 Controller

Figure 7 - Input Devices with PNP Semiconductor Outputs

Wire Output Devices

Figure 8 - Output Device Wiring

ATTENTION: Serious injury may occur due to a loss of required safety functions.

Do not connect loads beyond the rated value of safety or test outputs.

Do not use test outputs as safety outputs.

Wire the controller properly so that the 24V dc lines do not touch the safety or test
outputs.

Do not apply the power supply to the test output terminals.

Ground the 0V line of the power supply for external output devices so that the
devices do not turn on when the safety output line or the test output line is
grounded.

Separate I/O cables from high voltage or high current lines.

SmartGuard 600
Controller

V1

Tx

INx

G1

24V dc

24V dc

OSSDx

GND

4.5 mA Typical

SmartGuard 600
Controller

V2

G2

24V dc

OUTx

0.5 A Max

Load

Advertising