Function Blocks Command Reference

Appendix D

Two-hand Control Function Block Truth Table

In the truth table, 0 is off and 1 is on.

Two-hand Control Function Block Error Handling

A discrepancy error is generated when one of the inputs is not in its correct state
for longer than the discrepancy time. For example, in Dual Channel Equivalent
mode, both inputs must be active (on) within the discrepancy time or an error
occurs.

Use this table to diagnose and reset a Discrepancy Error condition in the Two-
hand Control function block.

(1) A discrepancy time check is not performed if 0 is set.

Table 21 - Truth Table for Two-hand Control Function Block

Input 1

(Pair 1 - NO)

Input 2

(Pair 1 - NC)

Input 3

(Pair 2 - NO)

Input 4

(Pair 2 - NC)

Output Enable

0

0

0

0

0

0

0

0

1

0

0

0

1

0

0

0

0

1

1

0

0

1

0

0

0

0

1

0

1

0

0

1

1

0

0

0

1

1

1

0

1

0

0

0

0

1

0

0

1

0

1

0

1

0

1

1

0

1

1

0

1

1

0

0

0

1

1

0

1

0

1

1

1

0

0

1

1

1

1

0

Table 22 - Error Detection and Reset for Two-hand Control Function Block

Error

Condition

Status When an Error Occurs

To Reset the Error Condition

Output

Enable

(1)

Fault

Present

Error Output

Discrepancy
Error at Pair 1

OFF
(Safety State)

ON

Discrepancy
Error Pair 1: ON

Remove the cause of the error and then
either:
1. Make both input pairs 1 and 2 inactive

and active again.

2. Change the controller’s operating mode

to Idle and back to Run.

Discrepancy
Error at Pair 2

Discrepancy
Error Pair 2: ON