User mode switch function block truth table, User mode switch function block error handling – Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual

Page 235

Advertising
background image

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

235

Function Blocks Command Reference

Appendix D

User Mode Switch Function Block Fault Present Output Setting

The Fault Present output can also be used in programming. To enable this
output, check the Use Fault Present checkbox on the In/Out Settings tab of the
Function Block Properties dialog box.

User Mode Switch Function Block Truth Table

In the truth table, 0 is off and 1 is on.

User Mode Switch Function Block Error Handling

Use this table to diagnose and reset a discrepancy error condition in the User
Mode Switch function block.

Table 24 - Truth Table for User Mode Switch Function Block

Inputs

Outputs

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

1

Table 25 - Error Detection and Reset for User Mode Switch Function Block

Error Condition

Status When an Error Occurs

To Reset the Error Condition

Output

Fault

Present

More than 1 input was on for
more than 2 seconds.

(1)

(1) If more than 1 input is on at the same time, the corresponding output of the first input to turn on will turn on for 2 seconds.

Off
(Safety State)

On

Correct the system so that only one
contact is on.

All inputs were off for more than
2 seconds.